Construction Design-Simple Air Sealing Strategies

I built my first home for a customer back in 2000, I’ve learned a lot since then.  One of the areas I’ve learned the most is in building tightness.  These days I’m working more as an energy auditor.  Conducting code compliance blower door testing on new homes and conducting energy audits, some with blower door testing on older homes.  I get to see where homes leak.  I live in climate zone 7.  With 10,000 heating degree days and usually fewer than 500 cooling degree days, builders in my area get away with using polyethylene sheeting as both an air and vapor control layer.  Most new homes I blower door test achieve a 2-2.5 air changes per hour at 50 Pascals (ACH50).  Our houses survive because of a requirement for balanced mechanical ventilation.  Take the poly away, and most builders will struggle passing the blower door test.  Though we can do it, not every home needs to be passive house tight (.6 ACH50).  Getting air tightness to around 2 ACH50 for the majority of new construction is perfect.  How can we get there?  Well, here are my suggestions.

1.  Determine the location of the air control layer that best suits the needs of the project.  Sometimes that can be inside, often it’s better outside.  Maybe it’s both.  The projects I work on, I try to make it both. A belt and suspenders approach.  I do like using the exterior as the main air control layer, to me, it’s easier to detail.

2.  The air control layer needs to be continuous.  The red line test is a good way to determine if you’ve missed something.  Take a red pen and trace around any section drawing, the pen should never leave the paper as you outline the location of the air control layer.  How is the foundation sealed to the wall?  The wall to the window or door?  The wall to the roof or ceiling, and so on.  An unthought of disconnect is a potential air leak.

3.  You need to set a goal for a tightness level.  Many areas of climate zones 3-7 have adopted a code minimum of 3 ACH50.  If the code is not enforced in your area,  3 ACH50 should still be the minimum and the home needs to be tested.  The lower the blower door test result, the more efficient, comfortable and healthy the home becomes.  Another reason for a tight home is the possibility of reducing the size of the heating and cooling equipment.  One piece of information needed for an accurate heat loss is the air infiltration rate.  Set a goal and communicate with your HVAC contractor early in the project so that equipment is sized correctly.  Try to better the blower door test results with every home.

Air sealing doesn’t require any exotic materials, though some can be used if you want (some of the European tapes are awesome).  The essentials are a good quality tape, acoustical caulking and canned spray foam.  There are a few areas I really like using closed cell spray foam, but you can get by without with a little extra attention paid to these areas.  When planning an air sealing strategy, I start at the foundation and move up in the assemblies. I work my way through the structure just as I would if I were building it.

1.  The foundation to wall connection.  Homes in my climate, especially in the heating months, leak low and high.  The stack effect draws cold air into the home at the lower levels and exhausts warm air out at the higher levels. The larger the difference between indoor and outdoor temperatures, the stronger the stack effect, I’ve experienced 120°+F differences in my climate. Sealing the bottom plate is critical.  I’ve talked with many builders who only use an adhesive such as PL400 for the connection between the concrete to the treated bottom or sill plate.  This is not only a poor air-seal, it is not an effective measure to prevent capillary action or drawing moisture from the concrete up into the wall framing.  There are some great methods for this connection out there, I like to keep it simple.  Install the sill seal between the concrete and bottom plate.  Seal the exterior with a tape or liquid flashing that will bond to both the wall sheathing and whatever material is below.  This could be concrete, wood or foam insulation.  Next, seal the inside concrete slab or subfloor to framing using an acoustical caulking right before the vapor control layer or drywall is installed.

Air leaking under a bottom plate during a blower door test.

The following pictures are how I addressed this connection at my own home (a 1952 Cape).  I used Henry Blueskin VP100 and wrapped the self-adhered membrane onto my foundation.  I increase the adhesion by priming the concrete with Henry Blueskin Prep, a spray adhesive.  It’s now been in place for a year, I still can’t pull the Blueskin from the concrete foundation.  I also seal the inside of the wall to floor connection using a large bead of acoustical caulking. I wait to install this bead until right before the vapor control layer or drywall is installed.  Acoustical caulking is sticky stuff and tends to be messy.  Waiting to install until right before it’s covered will keep any sub-contractors working on the job from being mad at you.

 

Air sealing the bottom plate on my home.

This process could also be accomplished by using a fluid applied caulking. Because of the irregular surface that needed to be both water and airtight, Prosoco’s Fast Flash was chosen. We were able to work it into the nooks and crannies of the ICF/concrete transition and the wall sheathing.

Air sealing the sheathing to concrete foundation at the slab less slab on grade home.

2. The wall sheathing is the next detail to air seal.  If using a sheathing with an integral water resistive barrier, such as Huber’s Zip or LP’s Weatherlogic, you will be using their tapes to create a water and air-tight seal.  What if you are using a standard OSB or plywood?  You could also tape those seams before the installation of a mechanically fastened WRB. Then cover the sheathing with your choice of housewrap or WRB.  Follow the manufacturers installation instructions for the rest of the WRB installation.  Because the foundation to sheathing connection has already been treated by tape or a fluid applied product, do not seal the bottom of the WRB.  If any bulk moisture should end up behind the WRB, it should freely drain out the bottom.  If you’re using a fully adhered or liquid applied WRB, those products will provide air sealing.  My personal home, still a work in progress, has many more wood joints than the typical new build of today.  The home is sheathed with individual boards or shiplap. I decided to use a fully adhered WRB for air sealing.

Fully adhered water resistive barrier over shiplap at my home.

3. The next detail is how to keep the exterior air barrier continuous at the top of the exterior wall.  If your building the “perfect wall” where rafter tails will be added after a layer of continuous exterior insulation, the air control layer will simply follow up the roof at the sheathing layer.  Most homes being built today have rafter tails already built into the rafter.  This forces us to move the air control layer to the interior ceiling.  This can be accomplished by either a tape, mechanically fastened or fully adhered WRB connected to the exterior wall WRB Extend the product up and over the top plate and seal to the interior ceiling air barrier.  This interior air control layer might be drywall installed airtight.  If the budget will allow, it could also be a smart vapor barrier such as Siga’s Marjex, Pro Clima’s Intello or Certainteed’s MemBrain.  In my climate, I’m not afraid to use a 6-mil poly on the ceilings as long as the space above is an unconditioned and vented attic.  With cathedral ceilings and unvented attic assemblies, I would choose one of the other mentioned methods.

Tape over the top plate extending the exterior wall air control layer with the interior ceiling air control layer.

The connection where the wall meets the ceiling along with interior ceiling penetrations is where I see the most problems during blower door testing.  I have hundreds of thermal images I could show where air is leaking into the home.  In my very cold climate, the stack effect moves warm air out those holes and into attic spaces.  Best case scenario is some lost heat, worse case, moisture with the air leak is unable to clear the vented attic space and finds a condensing surface.  The frost that forms melts during warmer weather. I’ve heard this process called “attic rain”.  Never a good sign when moisture is dripping from the ceiling inside the home.

Air leaking at interior wall to ceiling connection during a blower door test.

4. The biggest holes punched through the air control layer are windows and doors.  These first need to be integrated into the water resistive barrier (WRB).  Controlling water is more important than controlling air.  The installation method will depend on the chosen WRB.  When using an exterior air control method, it’s important that the product is extended into the window or door opening. Air can easily move through framing connections around the opening.  By extending the tapes or fluid applied sealants through the opening will allow for a continuous air control layer after the window is installed.  A minimal expanding spray foam or backer rod and caulk applied from the interior will complete the continuity of the air seal with the window.

Air sealing a window opening using Zip’s Liquid Flash to seal the framing connections and sheathing to framing connection. Tapes or other sealants may also be used.

5. How about exterior penetrations.  Electrical wires, water spigots, HVAC vents can all punch holes through the air control layer.  There are a lot of different methods that can be used to seal these.  Tapes, gaskets, fluid applied sealants and caulks can all be used.  I like products that don’t have to be reapplied in the future.  My first choice is a quality tape. If there may be some movement of the material penetrating the air barrier, such as a PVC vent for a high efficiency heating appliance, I would choose a gasket. Electrical wires can present a different challenge.  There are often many wires for exterior lighting and outlets poking out. Jake Bruton has a great solution, one hole, one wire.  It’s hard to make a good air seal around multiple wires in the same hole. One hole, one wire is the best solution.

Tapes and gaskets used to air seal penetrations through the exterior air control layer.

6. Another area I see air leakage during blower door tests are penetrations through the air control layer on the interior.  Electrical boxes, plumbing pipes and HVAC ducts can all be a problem in both walls and ceilings.

All penetrations leading from the conditioned space of the home into an unconditioned attic or crawls space need to be sealed.  Back to the Jake Bruton method, one wire, one hole.  I typically use canned expanding spray foam, but caulks and other sealants can be used.

Using airtight electrical boxes with a foam gasket provide some reduction in air movement.  Most airtight boxes don’t have a good air seal where the wires enter the box.  Often this area is sealed with caulking or expanding spray foam.  I recently used an airtight box that had a chamber where the wires entered which could be spray foamed shut.  A nice option.

Stay away from the traditional recessed cans in exterior ceilings.  Even though many have improved the air tightness of the can, the connection to the ceiling air control layer still requires good execution.  And then there’s the insulation that is being displaced.  There are much better options available.

I’ve never been a fan of running ductwork in unconditioned attic spaces. How the ductwork gets into the space and how the distribution boot is sealed to the air control layer make all the difference.  Often the air sealing around these pipes and boots aren’t effective and can be seen while blower door testing.  My suggestion, find a way to keep the ductwork inside the conditioned space.

Lastly, plumbing pipes.  Typically, these are PVC vent pipes that extend through the top plates and into the attic space.  Using caulking or spray foam to seal between the pipe and the framing is usually effective at stopping air. I still occasionally find these are a problem in new construction.

The typical airtight electrical box. The foam gasket does not effectively stop air moving through the point of were the wires enter the box. An additional air sealing method is required for this area. Can be difficult to air seal.

This electrical box, called Air Foil, has a second chamber where the wires penetrate the box. This chamber is then air sealed using expanding foam. The flange seals to the drywall or other interior air control layer by a bead of acoustical caulking.

Leaking recessed can during blower door test.

Ductwork from an unconditioned attic through the top plate of wall framing.

One piece of advice I did not mention in this article is how to properly install tapes. All tape manufacturers require the tape to be either rolled or other mechanical pressure applied to “wet” the tape.  This forces the adhesive of the tape into all the small voids of the surfaces being taped. Depending on the location, this may also be a critical step in keeping water out of the home. Hand pressure isn’t enough.

Roll the tape!

I definitely see improvements in blower door test results from the homes built in the 1950’s, such as mine and the new homes of today.  My home tested at 12.5 ACH50.  Homes from the 1980’s, when polyethylene sheeting on the warm in winter side of the wall and ceiling assemblies began to be widely used in my area, often test less than 5 ACH50.  The average new home I test today is closer to 2 ACH50, and I’ve tested several at 1 ACH50. Only one of these homes tested at 1 ACH50 I would consider to be “high performance”.  As we continue to gain experience in how to improve the tightness of a home, we also need to challenge ourselves.  If your homes are testing at 2 now, make an effort to get to 1.5 ACH50.  I believe the codes will eventually begin to force lower blower door numbers, there will be less of a struggle if you’re already achieving a low level of air tightness.


This article has been about basics of air sealing.  Two additional points need to be considered when building a tight home. First is controlling interior moisture levels and improving indoor air quality and the second is the possible need for an exterior rain screen depending on the type of siding used.  Two topics for cold and very cold climate construction I’d like to address in future articles.